Electrical Insulating Rubber Mat (As Per IS:15652/2006)

Human safety is the prime concern of the mat developed for electrical purpose and shall be used as floor covering for the protection of workers on AC & DC installations with the system voltages upto 66 kV ac & 240 V dc.

CONSTRUCTION
Rubber Composition : Insulating Mat made for Highly Electrical resistant Elastomer, free from any insertions (includes rubbers, latex and Elastomeric compound that may be natural or synthetic or a mixture or a combination of both)
     
Reinforcement : Upper surface of the mat is having small anti-skid aberration marks (rough surface without edges) to avoid slippery effects and lower surface is plane.
     
Size : a) Length & Width : Standard sizes are 01 x 02 & 1.2 x 2.4 Mtrs.
b) Thickness as per classification & designation*
Sr. No. Class of Mat Thickness (mm) Tolerance (%) ac (rms) kV dc (rms) V
1. A 2.0 ± 10 3.3 240
2. B 2.50 ± 10 11 240
3. C 3..0 ± 10 33 240
4. D 3.50 ± 10 66 240
 
ELECTRICAL PROPERTIES VOLTAGE TESTS
Sr. No. Class of Mat Thickness (mm) Di-electric Strength ac (rms) kV Proof Voltage ac (rms) kV
1. A 2.0 30 10
2. B 2.50 45 22
3. C 3..0 65 36
4. D 3.50 110 70
 
WORKING TEMPERATURE RANGE
-10 to 55º C
 
SALIENT FEATYRES OF THE MATS
1. Flame Retardant
2. Low Temperature Resistance
3. Acid/Alkalis & Oil Resistant
4. Insulation Resistance with water
5. Low leakage Currentº C
 
AREAS OF APPLICATIONS/USE
1 All kind of electric Sub-Stations
2. Transformer rooms
3. Lift Machine Rooms
4. Switch Rooms,
5. electrical panels
6. AC Plant Rooms
7. X-Ray Plant Rooms
8. LT/HT Labs
9. Around Bus Bars
10. Generator Rooms etc.
 
RECOMMENDATIONS OF USE OF MATS
  • For obtaining max. practical safety in adverse working conditions, the mat should be permanently pasted with the help of suitable adhesive/resin.
  • All joints and covers shall be filled/covered with insulating materials of matching colours.
  • Joints waterproofing compound should be used to protect insulating & electrical properties from moisture.
  • Contact with petrol/diesel/paraffin or white spirit and strong acid/alkalis should be avoided.